Atlas SCT Testbeam Shift Instructions (May 2002)

Gareth Moorhead


Contents

Introduction

These notes are intended to be a brief guide to operating the SCT tesbeam facility at the CERN SPS H8 beamline (in the "North Area" Prevessin site, Building 887 (EHN1), Phone 76733). We are in barrack HNA257, which is on the lower floor of the large experimental hall EHN1 (building 887), on the side towards the Saleve.
The testbeam setup is highly changeable as equipment comes and goes, so these notes may be incomplete or out of date. It is therefore advisable to visit the control room before your first shift in any testbeam period for a briefing on the latest details.

Shift Duties

Generally during the course of the shift:
How to do a Scan

The procedure for doing a scan is as follows.
DAQ Control

TBDAQ is a companion to SCTDAQ, and uses SCTDAQ services whenever module configuration as required. To start a TBDAQ session from scratch:
HV Control

In 2001, we use SCTHV for detector bias. These are red or pink modules in the VME crate with four channels.

To set the bias voltages for a Bias Scan point, use the macro "TBSetBias(Vunirr, Virr)". This will configure the modules to the required voltages for the unirradiated and for the irradiated sensors, and then execute a HVRamp(). E.g., for nominal conditions, "TBSetBias(150,350)".

Bias voltages can also be set using SCTDAQ functions, e->ConfigureVariable(mod,typ,val) followed by e->HVRamp(0) or pressing the HVRamp button. For Vdet, typ is 30; for Idet (current limit in uA) the typ is 60.

Do not forget to use the "HVStatus" button to check that the HV is really ramping. Also monitor the LEDs on the actual SCTHV modules - they should be on, and not blinking..


Magnet Control

The Magnet terminal is in the next control room, near the Pixel electronics. It is an old PC in rack R25 with an aluminium panel above.

On the panel, the LEDs for "CT4" should be ON, and for "CT5" OFF. If CT4 is off, press "CT4 START".

On the PC, there should be a large LabVIEW window. If not, click the icon to start it.

For all magnet operations, several steps are required. ALWAYS wait till one step is finished before starting the next.

To switch ON the magnet:

To switch OFF the magnet, reverse the above procedure.

If there is an interlock problem, go to the Interlock panel, and click "Read". If this doesn't help. do "Load" and load the "intlcks" file. If this still doesn't help. call CRN or one of the magnet experts .

Ramping the full 5000A, either up or down, takes a long time, about 30 minutes.


Angle

To set the angle, first take an access. Climb to the rear of the black SCT chamber, and turn the small handle until the scale reads the required setting in millimetres for the angle inside the box. The scale is read at the join between the aluminium and brass support pieces, on the side further from the box.

Note: if you are unhappy about climbing into the magnet with it switched on, then take the time to ramp the magnet down.


Access

To open the zone, go to the SPS terminal, "eanorth>". There should be a "NODAL" window. If not, restart the terminal. In the NODAL window, you should have a "TREE" prompt. If not, do "RUN TREE" (in capitals).

Do "ACCESS", then "OPEN". Our door is 158. Don't forget to enter your name. Check that something is happening on the terminal screen.

After about 5 minutes, the door goes to "Access with Key". Take a key, go inside, come back, return the key, and press "End of Access".

Then go to the terminal, do "ACCESS", "BEAM ON", door 158 and your name.

If there seem to be problems, eg, a very low raw trigger rate (scalers 1 and 2) after the beam should be on, then call CRN. Likely that a magnet has tripped or the beam blocker hasn't properly moved.

If you see the message "Veto on Chain H8" after ending access, don't worry. This just means you haven't waited the few minutes it wants to ensure that anybody left inside the zone can see the warning lights and get out. Wait one minute and then try again.


Cooling & Chiller Control

In 2001, we use two Huber chillers, one to cool the chamber base plate and N2 gas, and the other to supply cold fluid directly to the modules. These chillers will usually be set to -25C, resulting in displayed fluid temperatures around -20C depending on heat load and insulation.

The Huber temperature is set by pressing "Set", then up or down arrows, then "Set" again. Make sure the Huber power switch is in "II" mode (cooling & pump), rather than "0" (off) or "I" (pump only).
Temperature Sensing

In 2001, environment temperature monitoring is by:

suggestions/corrections